Skip to content

General

The REVVE pre-magnetisation unit is used to prevent inrush currents in large transformers. A special method, using a pre-magnetisation unit and a contactor circuit, allows transformers rated up to 800 kVA (and above) to be switched free of inrush current. In combination with the REVVE, even large transformers can be protected on the primary side with fast-acting fuses rated at the rated current. The primary-side fuse then provides both short-circuit and overload protection.

Design

The main transformer is pre-magnetised by means of a small pre-magnetisation unit, a contactor circuit and control electronics, and can then be switched without inrush current. The control electronics drive up to three external contactors. The first contactor activates the pre-magnetisation unit. The second contactor bridges the pre-magnetisation unit and switches the load transformer fully on. The third contactor is optional and switches the output of the load transformer through, since this method of preventing inrush current works best with load transformers off-load. Because external contactors are used, the REVVE can be used in both single-phase and three-phase applications.

Technical Specifications

Supply voltage: 400 V to 690 V ±10% (single-phase or three-phase). Supply frequency: 50/60 Hz ±10% (45 … 65 Hz). Ratings: up to 800 kVA (higher ratings on request). Ambient temperature: -20 °C … +70 °C. Humidity: 95% (non-condensing). Degree of protection: IP00 (other degrees of protection possible on request). Connections: terminals (screw connection).