Skip to content

General

  • The transformer switching relay (REVRL) is used for the smooth switching of one or more single-phase transformers, off-load or on-load, without inrush current. The soft switch-on method prevents the inrush current rather than merely limiting it, as conventional inrush current limiters do.
  • The REVRL is simply connected between the mains switch and the transformer. It can also be used as the mains switch itself if it is operated via the control input (in this application there is no galvanic isolation).

Applications

The REVRL is used, for example, with isolating, control, heating and vehicle transformers, and in industry, plant engineering and research. Suitable for inductive and capacitive loads.

Functions

  • Soft switch-on method
  • Before switching fully on, the REVRL pre-magnetises the transformer with unipolar voltage pulses. The strength of the pre-magnetisation is the same for every transformer and should reach a
  • reversal point of the hysteresis curve. The width of the voltage pulses needed for this must be matched to the different transformer types, such as stacked-core or toroidal-core transformers. The potentiometer (TP1) in the REVRL serves this purpose.

Further options and versions available on request