RIPCUSV 10D

  • DC UPS module for supplying industrial PCs (IPC)
  • IPC UPS module with 10 A
  • Input cut-in voltage threshold DC 20.6 V
  • Output DC 24 V
  • USB interface for communication between the UPS and the IPC
Request a custom solution
RIPCUSV 10D — DC UPS module for powering industrial PCs (IPC)

General

As an addition to our RDCUSV range we offer the RIPCUSV 10D. These RIPCUSV modules are fitted with a USB interface. Together with an industrial PC (IPC) supplied with DC 24 V and running the Microsoft Windows NT/2000/XP/Vista/W7 operating system, they allow a computer-controlled uninterruptible power supply to be built. The UPS communicates with the IPC over the interface. Once the UPS time has elapsed, the IPC receives a signal on which it shuts the system down. As soon as the computer has shut down it reports this to the UPS, which then switches off the supply voltage to the computer. Comprehensive software is supplied with the unit.

  • The technology of our DC UPS modules makes it unnecessary to use switching regulators such as boost converters. EMC problems therefore do not arise.
  • All Riedel IPC UPS modules have a compact design with the battery inside the housing and are easy to install. The IPC UPS modules snap onto DIN rail. In use they are connected to the DC output of a DC 24 V power supply unit (see block diagram) and the “AUS” terminal is connected to the negative terminal.
  • The module's electronics monitor the output voltage and switch the battery in when the voltage falls below the preset threshold. The internal battery supplies the load for a defined period at a maximum current of 10 A, which is limited internally. The output voltage is regulated to the threshold value. LEDs are fitted for visual monitoring and indicate ready (green), UPS operation (yellow) and battery undervoltage (red).

Function

  • Output voltage stabilised in the event of a mains failure (DC 20.6 V)
  • Adjustable boot-time bridging (2-5 min)
  • Adjustable UPS time (1 s to 60 min), then a signal to the IPC via the USB interface or RS232
  • The UPS is switched off by a signal from the computer; automatic shutdown after an adjustable delay (30 s to 10 min)
  • Short-circuit proof
  • Automatic shutdown on: • battery undervoltage (DC 17 V)
  • Automatic charging • IU characteristic
  • Daily battery test (automatic) and notification in the event of a fault.
  • The software can run scripts automatically
  • Extensive logging function in the software