Skip to content

RDCUSV 10D – 40D

DC UPS modules

  • DC UPS modules up to 40 A
  • Input cut-in voltage threshold DC 22 V or DC 20.6 V
  • Output DC 24 V
  • Back-up time at maximum current factory-set to 30 s (other back-up times optional)
Request a custom solution
RDCUSV 10D – 40D — DC UPS modules

General

  • Disturbances on our power supply networks are a fact of life today. They can account for up to 10% of total operating time. Voltage fluctuations and dips occur, and in rarer cases complete outages, caused for example by a lightning strike or by an error during maintenance work. A suitable UPS system provides protection against disturbances of this kind.
  • Under EN 61131-2 (limits for the rated DC voltage at DC 24 V), the operating voltage for electronic controls is currently DC 24 V (DC 20.4 V – DC 28.8 V eff.). Power supply units must be rated accordingly.
  • For this purpose we offer DC UPS modules to go with our DC power supplies. They can be connected in parallel on the secondary side without difficulty and so give your controls reliable protection while remaining simple to handle.
  • The technology of our DC UPS modules makes it unnecessary to use switching regulators such as boost converters. EMC problems therefore do not arise.
  • All Riedel DC UPS modules have a compact design with the battery inside the housing and are easy to install. The DC UPS modules snap onto DIN rail to DIN EN 60715. The module is available in the versions DC 24 V 3 A 30 sec, DC 24 V 10 A 30 sec, DC 24 V 20 A 30 sec and DC 24 V 40 A 30 sec. Further versions are available on request.
  • In use, the module is connected in parallel with the DC output of a DC 24 V power supply unit (see block diagram) and the “AUS” (off) terminal is connected to the negative terminal. When the system is switched off, the “AUS” connection must be opened by the normally-open auxiliary contact of the main switch in order to deactivate the UPS module!

Option

Back-up time limiting can be switched off, allowing longer UPS times