Skip to content

RFDr

Three-phase filter circuit chokes

Filter circuit chokes are used in reactive power compensation systems. Together with the capacitors of the system they form a series resonant circuit, preventing resonance with the harmonics present in the supply.

Request a custom solution
RFDr — Three-phase filter circuit chokes

General

  • Rated voltage: 3 AC 400 V
  • Rated current: 3.6 to 72.2 A
  • Detuning factor: 7%
  • Resonant frequency: 189 Hz
  • Rated frequency: 50 Hz
  • Degree of protection IP00
  • Insulation class E
  • Ambient temperature 40 °C

Features

  • Compact design, low weight
  • High reliability and long service life

Standards

  • Kleindrosseln nach VDE 0570 Teil 2-20, DIN EN 61558-2-20

Design

Open, upright design, for stationary use, for installation in equipment and mounting in dry rooms. Connection to tracking-resistant transformer terminals with screw and blade connection (up to 12.5 kvar). Above 12.5 kvar and up to 25 kvar, universal terminal blocks with screw connection are used; from 30 kvar, cable lugs. The terminals are finger- and back-of-hand safe to UVV (BGV A3). Fitted with a thermal switch in the centre coil. Other versions available on request.