DRUL UL-CSA(-A)
Three-phase transformer
Three-phase transformers approved for the North American market, where they are used as industrial control transformers. They also meet national and international regulations for worldwide use.

General
- Rated power 0.11 to 50.0 kVA
- Rated input voltage: 200 to 600 VAC (max. 660 V with tapping)
- Rated output voltage: 10 to 600 VAC (max. 660 V with tapping) for 0.11 – 6.0 kVA; 20 to 600 VAC for 7.50 – 10.0 kVA; 40 to 600 VAC for 12.0 – 25.0 kVA; 80 to 600 VAC for 30.0 – 50.0 kVA
- Degree of protection IP00
- Insulation class F
- Ambient temperature 40 °C
- Voltage freely selectable by the customer
- Four separate secondary windings, the sum of which must lie within the specified voltage range
- High reliability and long service life
- Low total losses, high efficiency
- High output voltage stability
Standards
- Mains transformer to:
- VDE 0570 Part 2-1, DIN EN 61558-2-1, UL 5085 / CSA 22.2
- Isolating transformer to:
- VDE 0570 Part 2-4, DIN EN 61558-2-4, UL 5085 / CSA 22.2
- Safety transformer to:
- VDE 0570 Part 2-6, DIN EN 61558-2-6, UL 5085 / CSA 22.2
- Autotransformer to:
- VDE 0570 Part 2-13, DIN EN 61558-2-13, UL 5085 / CSA 22.2
Design
Open design, for stationary use, for installation in equipment and mounting in dry rooms. Connection to tracking-resistant transformer terminals with screw connection. The transformer terminals are finger- and back-of-hand safe to UVV (BGV A3). Suitable for installation up to IP23 with natural air cooling.