Primary switched-mode power supply, regulated / battery charger

  • Primary switched-mode single-phase power supplies, regulated
  • available in 30 W, 60 W, 125 W, 250 W, 480 W and 960 W
  • Input, wide input voltage range 85-264 V, 90-264 V, 196-460 V (depending on version) — see data sheet
  • Output DC 12, 24 or 48 V
Request a custom solution
RPL 122.5W-2440W — Primary switched-mode power supply, regulated / battery charger

General

Primary switched-mode power supplies require no mains transformer and are compact and lightweight.

Key features of the RPL series

  • Universal input (AC or DC on single-phase units, 3 AC or DC on three-phase units) with a wide input voltage range
  • Output voltage adjustable over a wide range via a front-panel potentiometer
  • RPL series power supplies can be used as chargers (type …WL)
  • Temperature-compensated battery charging is activated either by repositioning the jumper on the 250 W single-phase, 480 W single-phase and 480 W three-phase units, or by specifying option –T on the other chargers together with a temperature sensor (10 kOhm NTC thermistor) fitted at the battery. This optimises charging where the ambient temperature varies widely and, among other benefits, extends battery life
  • Can be connected in series and in parallel
  • 25% power boost for 4 s under peak loads
  • Protection against overload, short circuit, overvoltage and overtemperature
  • Three-colour status LED on units from 125 W: green – voltage regulation, red – current limiting, yellow – unit connected to the supply, output voltage switched off
  • Volt-free fault signal contact (changeover)

Options

-S:
decoupling diode (series diode) at the output, for straightforward construction of redundancy and UPS systems;
-U:
analogue input DC 0-10 V for adjusting the output voltage from 0 to Uout max;
-D:
Overload Shut Down — latching shutdown on overload;
-P:
balanced power sharing in parallel operation;
-T:
temperature-compensated charging;
-F:
remote on/off switching;
-A:
fault signal contact (alarm);
-M:
sub-zero temperature range. Relevant only for the RPL 2440D, as the other units are designed for sub-zero temperatures as standard;
-C:
mains harmonic limitation to EN 61000-3-2 Class C (lighting equipment).